12HD-140
CCB12HD-140

  FEATURES
FOR UPS STANDBY
POWER APPLICATIONS
(12V33AH@20HR RATE)
(12V140Watts/Cell@15Min Rate)
 
*Flame-arresting one-way pressure-relief vent for safety and long life.
*Can be used in any orientation. Upright, side or end mounting recommended
* Absorbent Glass Mat(AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance
* Computer-grnerated grid design optimized for high*power density
* Float/Cycle Use
* Useable in Any Position
* Thermally welded case-to-cover bond to eliminate leakage.
* Long service life. Maintenance-free operation
* UL-recognized component
 
Download PDF data of this item for more information.
Nominal Voltage
Rated Capacity
@20hr Rate
Maximum Charge Rate
Maximum Discharge
Amps 5 sec.
Internal Resistance
12V
33Ah
17Amps
500Amps
6Mili Ohms
Capacity @ 77°F [25°C]
137 watts per cell@15min. Rate to 1.67 volts per cell
33Ah @ 20Hr. Rate to 1.75 volts per cell
30Ah @ 10Hr. rate to 1.80 volts per cell
29Ah @ 5Hr. rate to 1.75 volts per cell
25Ah @ 1Hr. rate to 1.75 volts per cell
Dimensions
Length
195mm [7.68in]
Width
130mm [5.12in]
Height
164mm [6.44in]
Total Height
180mm [7.07in]
Weight
12kg [26.45lbs]
Operating Temperature Range
Discharge
-4°F [-20°C] to + 140°F [60°C]
Charge
14°F [-10°C] to + 122°F [50°C]
with temperature compensation
Recommended Operating Temperature Range
68°F[20°C] to 77°F [25°C]
Charging [Constant Voltage]
Cycle Use
Initial Current 6.5Amps [Recommended}
Float Use
Voltage 14.5-14.9Volts @ 77°F [25°C]
Voltage 13.6-13.8Volts @ 77°F [25°C]
Self Discharge @ 77°F [25°C]
Capacity after 3 month storage
90%
Capacity after 6 month storage
80%
Capacity after 12 month storage
60%
CCB Battery may be stored for up to 12 months at 77°F[25°C] and then a freshing charge is required. For higher temperatures the time interval will be shorter.
Capacity affected by Temperature @ 20 hr Rate
104°F [40°C]
102%
77°F [25°C]
100%
32°F [0°C]
85%
5°F [-15°C]
65%
Notice: The above data are average values, and could be obtained within 3 charge/discharge cycles. These are not minimum values.
CONSTANT POWER DISCHARGE CHARACTERISTICS AT 25°C/77°F
Voltage Per Cell
Discharge Time
End VPC
Discharge Time
5Min
10Min
15Min
20Min
30Min
40Min
50Min
1hr
2hr
3hr
5hr
8Hr
10hr
20hr
Battery Output Power (W)
Battery Output Power (Amp)
1.75V
273
172
132
110
81
66.3
56.0
1.85V
21.5
12.1
8.45
5.45
3.55
2.90
1.50
1.70V
282
175
135
112
82
67.1
56.5
1.80V
23.5
12.5
8.80
5.65
3.70
3.00
1.55
1.67V
283
178
137
133
84
67.5
57.2
1.75V
24.6
13.2
9.15
5.80
3.80
31.0
1.65
CCB BATTERY * * * POWERING YOUR FUTURE... ...