12HD-370
CCB12HD-370

  FEATURES
FOR UPS STANDBY
POWER APPLICATIONS
(12V100AH @ 20HR RATE)
(12V390Watts/Cell@15Min Rate)
 
*Flame-arresting one-way pressure-relief vent for safety and long life.
*Can be used in any orientation. Upright, side or end mounting recommended
* Absorbent Glass Mat(AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance
* Computer-grnerated grid design optimized for high*power density
* Float/Cycle Use
* Useable in Any Position
* Thermally welded case-to-cover bond to eliminate leakage.
* Long service life. Maintenance-free operation
* UL-recognized component
 
Download PDF data of this item for more information.
Nominal Voltage
Rated Capacity
@20hr Rate
Maximum Charge Rate
Maximum Discharge
Amps 5 sec.
Internal Resistance
12V
100Ah
52Amps
795Amps
2.3Mili Ohms
Capacity @ 77°F [25°C]
390watts per cell@15min. Rate to 1.67 volts per cell
100Ah @ 20 Hr. Rate to 1.75 volts per cell
85Ah @ 10 Hr. rate to 1.80 volts per cell
81Ah@ 5 Hr. Rate to 1.75 volts per cell
66Ah@1Hr. Rate to 1.75 volts per cell
Dimensions
Length
330mm [13.0in]
Width
175mm [6.89in]
Height
215mm [8.47in]
Total Height
220mm [8.67in]
Weight
32.5kg [71.65lbs]
Operating Temperature Range
Discharge
-40°F [-4°C] to + 160°F [71°C]
Charge
10°F [-23°C] to + 140°F [60°C]
with temperature compensation
Recommended Operating Temperature Range
68°F[20°C] to 77°F [25°C]
Charging [Constant Voltage]
Cycle Use
Initial Current 40 Amps [Recommended]
Float Use
Voltage 14.5-14.9Volts @ 77°F [25°C]
Voltage 13.6-13.8Volts @ 77°F [25°C]
Self Discharge @ 77°F [25°C]
Capacity after 3 month storage
90%
Capacity after 6 month storage
80%
Capacity after 12 month storage
60%
CCB Battery may be stored for up to 12 months at 77°F[25°C] and then a freshing charge is required. For higher temperatures the time interval will be shorter.
Capacity affected by Temperature @ 20 hr Rate
104°F [40°C]
102%
77°F [25°C]
100%
32°F [0°C]
85%
5°F [-15°C]
65%
Notice: The above data are average values, and could be obtained within 3 charge/discharge cycles. These are not minimum values.
CONSTANT POWER DISCHARGE CHARACTERISTICS AT 25°C/77°F
End VPC
Discharge Time
End VPC
Discharge Time
5Min
10Min
15Min
20Min
30Min
40Min
50Min
1hr
2hr
3hr
5hr
8Hr
10hr
20hr
Battery Output Power (W)
Battery Output Power (Amp)
1.75V
644.5
474.3
370.2
303.1
227.1
179.5
147.5
1.85V
55.0
31.0
22.0
14.5
10.0
8.30
4.10
1.70V
687.8
495.2
385.2
310.9
232.5
184.2
152.1
1.80V
58.0
32.0
23.5
15.5
10.5
8.50
4.15
1.67V
706.5
504.5
390.0
315.2
236.0
186.7
154.3
1.75V
65.5
33.5
24.8
16.3
11.5
9.00
4.20