12HD-91
CCB12HD-91

  FEATURES
FOR UPS STANDBY
POWER APPLICATIONS
(12V26AH @ 20HR RATE)
(12V91Watts/Cell@15Min Rate)
 
*Flame-arresting one-way pressure-relief vent for safety and long life.
*Can be used in any orientation. Upright, side or end mounting recommended
* Absorbent Glass Mat(AGM) technology for efficient gas recombination of up to 99% and freedom from electrolyte maintenance
* Computer-grnerated grid design optimized for high*power density
* Float/Cycle Use
* Useable in Any Position
* Thermally welded case-to-cover bond to eliminate leakage.
* Long service life. Maintenance-free operation
* UL-recognized component
 
Download PDF data of this item for more information.
Nominal Voltage
Rated Capacity
@20hr Rate
Maximum Charge Rate
Maximum Discharge
Amps 5 sec.
Internal Resistance
12V
26Ah
5Amps
500Amps
60Mili Ohms
Capacity @ 77°F [25°C]
91.5watts per cell@15min. Rate to 1.67 volts per cell
26.0Ah @ 20Hr. Rate to 1.75 volts per cell
24Ah @ 10Hr. rate to 1.80 volts per cell
23Ah@5Hr.Rate to 1.75volts per cell
17Ah@1Hr. Rate to 1.75 volts per cell
Dimensions
Length
164mm [6.46in]
Width
123mm [4.84in]
Height
174mm [6.85in]
Total Height
182mm [7.17in]
Weight
10kg [22.04lbs]
Operating Temperature Range
Discharge
-4°F [-20°C] to + 140°F [60°C]
Charge
-14°F [-10°C] to + 122°F [50°C]
with temperature compensation
Recommended Operating Temperature Range
68°F[20°C] to 77°F [25°C]
Charging [Constant Voltage]
Cycle Use
Initial Current 5.2Amps [Recommended]
Float Use
Voltage 14.5-14.9Volts @ 77°F [25°C]
Voltage 13.6-13.8Volts @ 77°F [25°C]
Self Discharge @ 77°F [25°C]
Capacity after 3 month storage
90%
Capacity after 6 month storage
80%
Capacity after 12 month storage
60%
CCB Battery may be stored for up to 12 months at 77°F[25°C] and then a freshing charge is required. For higher temperatures the time interval will be shorter.
Capacity affected by Temperature @ 20 hr Rate
104°F [40°C]
102%
77°F [25°C]
100%
32°F [0°C]
85%
5°F [-15°C]
65%
Notice: The above data are average values, and could be obtained within 3 charge/discharge cycles. These are not minimum values.
CONSTANT POWER DISCHARGE CHARACTERISTICS AT 25°C/77°F
Voltage Per Bat.
Discharge Time
End VPC
Discharge Time
5Min
10Min
15Min
20Min
30Min
40Min
50Min
1hr
2hr
3hr
5hr
8Hr
10hr
20hr
Battery Output Power (W)
Battery Output Power (Amp)
1.75V
155
110
88.3
72.2
56.0
45.5
38.5
1.85V
15.0
9.00
6.60
4.25
2.85
2.35
1.25
1.70V
168
115
90.2
73.1
56.5
48.0
39.0
1.80V
16.1
9.40
6.85
4.45
2.95
2.40
1.28
1.67V
175
118
91.5
75.2
57.0
46.5
39.0
1.75V
16.9
9.75
7.00
4.50
3.05
2.45
1.30
CCB BATTERY * * * POWERING YOUR FUTURE... ...