12v150Ah
CCB12CD-150

กก FEATURES
* Maintenance Free
* Leak Proof / Spill Proof
* Gas Recombination
* Absorbed Electrolyte
* Float / Cycle Use
* Low Self Discharge Rate
* Safety Valve
* Lead Calcium Alloy
* Useable In Any Position
* Rugged Design
* Available Flame Retardant Material (Optional)
 
กก กก กก
Nominal Voltage
Rated Capacity
@20hr Rate
Maximum Charge Rate
Maximum Discharge
Amps 5 sec.
Internal Resistance
12V
150Ah
75Amps
1100Amps
2.9Mili Ohms
Capacity @ 77°F [25°C]
150.00Ah @ 20 hour rate [7.50A] to 1.75 volts per cell
135.00Ah @ 10 hour rate [13.50A] to 1.75 volts per cell
117.00Ah @ 5 hour rate [23.40A] to 1.70 volts per cell
107.00Ah @ 3 hour rate [35.67A] to 1.67 volts per cell
82.00Ah @ 1 hour rate [82.00A] to 160 volts per cell
Dimensions
Length
480mm [18.90in]
Width
170mm [6.70in]
Height
240mm [9.45in]
Total Height
240mm [9.45in]
Weight
42.5kg [93.50lbs]
Operating Temperature Range
Discharge
-4°F [-20°C] to + 140°F [60°C]
Charge
14°F [-10°C] to + 122°F [50°C]
with temperature compensation
Recommended Operating Temperature Range
68°F[20°C] to 77°F [25°C]
Charging [Constant Voltage]
Cycle Use
Initial Current 13.20Amps [Recommended}
Float Use
Voltage 14.5-14.9Volts @ 77°F [25°C]
Voltage 13.6-13.8Volts @ 77°F [25°C]
Self Discharge @ 77°F [25°C]
Capacity after 3 month storage
90%
Capacity after 6 month storage
80%
Capacity after 12 month storage
60%
CCB Battery may be stored for up to 12 months at 77°F[25°C] and then a freshing charge is required. For higher temperatures the time interval will be shorter.
Capacity affected by Temperature @ 20 hr Rate
104°F [40°C]
102%
77°F [25°C]
100%
32°F [0°C]
85%
5°F [-15°C]
65%
Notice: The above data are average values, and could be obtained within 3 charge/discharge cycles. These are not minimum values.
CCB BATTERY * * * POWERING YOUR FUTURE... ...