Nominal
Voltage |
Rated
Capacity
@20hr Rate |
Maximum
Charge Rate |
Maximum
Discharge
Amps 5 sec. |
Internal
Resistance |
12V |
200Ah |
100Amps |
2000Amps |
2.2Mili
Ohms |
Capacity
@ 77°F [25°C] |
200Ah
@ 20 hour rate [10.00A] to 1.75 volts per cell |
180Ah
@ 10 hour rate [18.00A] to 1.75 volts per cell |
156Ah
@ 5 hour rate [31.20A] to 1.75 volts per cell |
142Ah
@ 3 hour rate [47.33A] to 1.75 volts per cell |
110Ah
@ 1 hour rate [110A] to 1.75 volts per cell |
Dimensions |
Length |
530mm
[20.87in] |
Width |
238mm
[9.38in] |
Height |
215mm
[8.47in] |
Total
Height |
220mm
[8.67in] |
|
Weight |
65kg
[143lbs] |
Operating
Temperature Range |
Discharge |
-4°F
[-20°C] to + 140°F [60°C] |
Charge |
14°F
[-10°C] to + 122°F [50°C]
with temperature compensation |
Recommended
Operating Temperature Range |
68°F[20°C]
to 77°F [25°C] |
Charging
[Constant Voltage] |
Cycle
Use |
Initial
Current 53.6Amps [Recommended} |
Float
Use |
Voltage
14.5-14.9Volts @ 77°F [25°C] |
Voltage
13.6-13.8Volts @ 77°F [25°C] |
Self
Discharge @ 77°F [25°C] |
Capacity
after 3 month storage |
90% |
Capacity
after 6 month storage |
80% |
Capacity
after 12 month storage |
60% |
CCB
Battery may be stored for up to 12 months at 77°F[25°C]
and then a freshing charge is required. For higher temperatures
the time interval will be shorter. |
Capacity
affected by Temperature @ 20 hr Rate |
104°F
[40°C] |
102% |
77°F
[25°C] |
100% |
32°F
[0°C] |
85% |
5°F
[-15°C] |
65% |
Notice:
The above data are average values, and could be obtained within
3 charge/discharge cycles. These are not minimum values. |
CCB
BATTERY * * * POWERING YOUR FUTURE... ... |