2v1500Ah
CCB2ND-1500

  FEATURES
2V1500Ah @ 10 HR Rate
* Maintenance Free
* Leak Proof / Spill Proof
* Gas Recombination
* Absorbed Electrolyte
* Float / Cycle Use
* Low Self Discharge Rate
* Safety Valve
* Lead Calcium Alloy
* Useable In Any Position
* Rugged Design
* Available Flame Retardant Material (Optional)
 
Download PDF data of this item
Nominal Voltage
Rated Capacity
@10hr Rate
Internal Resistance
2V
1500Ah
0.08Mili Ohms
Capacity @ 77°F [25°C]
1500.00Ah @ 10hour rate [150A] to 1.75 volts per cell
1380.00Ah @ 5hour rate [276A] to 1.75 volts per cell
1260.00Ah @ 3hour rate [420A] to 1.75 volts per cell
975.00Ah @ 1hour rate [975A] to 1.75 volts per cell
Dimensions
Length
400mm [15.75in]
Width
350mm [13.78in]
Height
345mm [13.59in]
Total Height
382mm [15.04in]
Weight
100kg 220lbs]
Operating Temperature Range
Discharge
-4°F [-20°C] to + 140°F [60°C]
Charge
14°F [-10°C] to + 122°F [50°C]
with temperature compensation
Recommended Operating Temperature Range
68°F[20°C] to 77°F [25°C]
Charging [Constant Voltage]
Cycle Use
Initial Current 16Amps [Recommended}
Float Use
Voltage 2.25VPC +/- 1%@ 77°F [25°C]
Voltage 2.40 @ 77°F [25°C]
Self Discharge @ 77°F [25°C]
Capacity after 3 month storage
90%
Capacity after 6 month storage
80%
Capacity after 12 month storage
60%
CCB Battery may be stored for up to 12 months at 77°F[25°C] and then a freshing charge is required. For higher temperatures the time interval will be shorter.
Capacity affected by Temperature @ 20 hr Rate
104°F [40°C]
102%
77°F [25°C]
100%
32°F [0°C]
85%
5°F [-15°C]
65%
Notice: The above data are average values, and could be obtained within 3 charge/discharge cycles. These are not minimum values.
CCB BATTERY * * * POWERING YOUR FUTURE... ...